ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error Nos. 44, 45, 46, 49, 153, and 154
Error No.
Description
Details
Causes
44
Master: 441
Slave 1: 442
Slave 2: 443
Outdoor unit
ambient air tem-
perature
sensor error.
Disconnection or short circuit of outdoor unit
compressor discharge temperature sensor.
1. Check the connection on the outdoor unit
PCB.
2. Thermistor shorted or opened.
45
Master: 451
Slave 1: 452
Slave 2: 453
Outdoor unit heat
exchanger pipe
temperature
sensor error.
Disconnection or short circuit of outdoor unit
heat exchanger temperature sensor.
46
Master: 471
Slave 1: 472
Slave 2: 473
Outdoor unit
compressor
suction piping
temperature
sensor error.
Disconnection or short circuit of outdoor unit
compressor suction piping temperature sensor.
1. Check the connection on the outdoor unit
PCB.
2. Thermistor shorted or opened.
3. Check suction sensor in cooling mode;
check hot gas sensor located near the heat
exchanger in heating mode.
49
Master: 491
Slave 1: 492
Slave 2: 493
Outdoor unit IGBT
/ IPM temperature
sensor error.
Disconnection or short circuit of outdoor unit
IGBT / IPM temperature sensor.
1. Check the connection on the outdoor unit
PCB.
2. Thermistor shorted or opened.
Error No.
Description
Details
Causes
153
Master 11: 531
Slave 1 12: 532
Slave 2 13: 533
Outdoor unit
upper heat ex-
changer
temperature
sensor error.
Disconnection or short circuit of outdoor unit
upper heat exchanger temperature sensor.
1. Temperature sensor is not connected
properly.
2. Temperature sensor is defective (discon-
nected or short circuited).
3. Defective outdoor unit main PCB.
154
Master 11: 541
Slave 1 12: 542
Slave 2 13: 543
Outdoor unit lower
heat exchanger
temperature
sensor error.
Disconnection or short circuit of outdoor unit
lower heat exchanger temperature sensor.
Is the sensor connected
to the PCB correctly?
Is the sensor value
correct?*
Connect the sensor to PCB
correctly.
Replace the sensor.
Replace corresponding
outdoor unit PCB.
Yes
No
No
Yes
,IWKHYDOXHLV!NȍRSHQRUȍVKRUWWKHUHLVDQHUURU
Sensor resistance value may vary with the temperature.
See below for the resistance values according to temperature
WROHUDQFH
$LUWHPSHUDWXUHVHQVRU) Nȍ) Nȍ) Nȍ
3LSHWHPSHUDWXUHVHQVRU) Nȍ) Nȍ) Nȍ