ERROR CODES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Error No. 51(1)
Error No.
Description
Details
Causes
511
Master: 511
Combination ratio
is out of range.
Value of total indoor unit capacity exceeds
allowable outdoor unit capacity specifications.
1. Total indoor unit capacity is more than
130% outdoor unit rated capacity.
2. Wrong communication cable / piping
connections.
3. Control error of slave outdoor unit DIP
switches.
4. Defective slave unit PCB power supply.
5. Defective outdoor unit PCB.
6. Failed Master outdoor unit main PCB can
also cause this error if it could not see the
slave outdoor unit.
Is the total indoor unit
capacity <130% of the
outdoor unit capacity on
the LGMV report?
No
Yes
Check if the DIP
switches below are set
to ON:
Slave 1: No. 6
Slave 2: No. 7.
No
Reset corresponding DIP switches.
Yes
Is the power to the
Slave PCB On (see if LED
is blinking)?
Yes
Nso
Quantity and capacity
of the installed indoor units
match the LGMV data?
Yes
Adjust the capacity of indoor
and outdoor units.
No
Check the communication
cables between indoor and
outdoor units.
Is the main power
supplied correctly
(Terminal Block T-N)?
Yes
No
Supply main
power again.
Are communication cables
between master / slave outdoor
units connected correctly?*
Check and replace PCB,
line fuse, transformer.
No
Reconnect cables.
Yes
Are error codes displayed
in the order below after the
power is reset? (Slave 2
ĺ
Slave 1
ĺ
Master).
No
Replace Master or Slave
PCB.
Yes
End
* Check communication cables between outdoor units in the following order:
PCB connections
ĺ
terminal block
ĺ
communication cables.