Error Code
Description
Details
Outdoor Unit
2
1
1
Master outdoor unit inverter board IPM fault error;
Inverter driver detects overcurrent; Error code is deter-
mined by overcurrent in any one phase of compressor.
• Detected by the CT sensor on the IGBT PC board.
• Overcurrent in compressor UVW phases.
• Damaged compressor.
• Damaged IPM on inverter board.
• Compressor disconnected.
• Damaged inverter board – input voltage too low. For 208-
230V: On 068 compressors = 143A for a minimum of 3
μ
s;
on 048 compressors = 96A for a minimum of 3
μ
s. For 460V:
On 068 compressors = 80 A for a minimum of 3
μ
s; On 048
compressors = 56A for a minimum of 3
μ
s.
2
1
2
Slave1 outdoor unit inverter board IPM fault error;
Inverter driver detects overcurrent; Error code is deter-
mined by overcurrent in any one phase of compressor.
2
1
3
Slave2 outdoor unit inverter board IPM fault error;
Inverter driver detects overcurrent; Error code is deter-
mined by overcurrent in any one phase of compressor.
2
2
1 Master outdoor unit inverter PCB AC input overcurrent
(RMS) error.
• Overcurrent of outdoor unit inverter board PCB.
• Under voltage.
• Refrigerant flow restriction from defective EEV.
• Refrigerant charge is too high (overcharged).
2
2
2 Slave1 outdoor unit inverter PCB AC input overcurrent
(RMS) error.
2
2
3 Slave2 outdoor unit inverter PCB AC input overcurrent
(RMS) error.
2
3
1
Low DC voltage sensed at the master outdoor unit
inverter compressor DC link.
System shut off because the DC link voltage fell below 50V (for
both 208-230V and 460V units), or exceeded 550V (for 208-
230V units) or 1,000V (for 460V units) for a minimum of 250
μ
s.
• Start diagnosis at the inverter socket on the outdoor unit noise
filter PCB.
• There is a capacitor that is not working properly, or the voltage
at the capacitor is out of range.
• Disconnected DC link.
• Damaged electrical condenser component (serving capacitor)
on inverter driver board.
2
3
2
Low DC voltage sensed at the slave1 outdoor unit
inverter compressor DC link.
2
3
3
Low DC voltage sensed at the slave2 outdoor unit
inverter compressor DC link.
2
4
1 System has been turned off by the master outdoor unit
high pressure switch.
Master outdoor unit high pressure switch error.
• Check the connection on the outdoor unit PCB.
• Use chart in Troubleshooting section of the manual to check
signal output (V DC) versus actual pressure.
2
4
2 System has been turned off by the slave1 outdoor unit
high pressure switch.
Slave1 outdoor unit high pressure switch error.
• Check the connection on the outdoor unit PCB.
• Use chart in Troubleshooting section of the manual to check
signal output (V DC) versus actual pressure.
2
4
3 System has been turned off by the slave2 outdoor unit
high pressure switch.
Slave2 outdoor unit high pressure switch error.
• Check the connection on the outdoor unit PCB.
• Use chart in Troubleshooting section of the manual to check
signal output (V DC) versus actual pressure.
2
5
1 Input voltage to the master outdoor unit is too high or
too low.
0DVWHURXWGRRUXQLWKDVDQLQSXWYROWDJHRI9RU9
IRU9XQLWVRUDQLQSXWYROWDJHRI9RU9IRU
460V units).
2
5
2 Input voltage to the slave1 outdoor unit is too high or
too low.
6ODYHRXWGRRUXQLWKDVDQLQSXWYROWDJHRI9RU9
IRU9XQLWVRUDQLQSXWYROWDJHRI9RU9IRU
460V units).
2
5
3 Input voltage to the slave2 outdoor unit is too high or
too low.
6ODYHRXWGRRUXQLWKDVDQLQSXWYROWDJHRI9RU9
IRU9XQLWVRUDQLQSXWYROWDJHRI9RU9IRU
460V units).
2
6
1 Master outdoor unit inverter compressor operation error.
Inverter compressor failed to start.
2
6
2 Slave1 outdoor unit inverter compressor operation error.
2
6
3 Slave2 outdoor unit inverter compressor operation error.
2
9
1 Master outdoor unit inverter compressor overcurrent error. • Outdoor unit inverter compressor current draw is too high.
• Compressor defect and restriction in refrigerant piping are
possible causes.
2
9
2 Slave1 outdoor unit inverter compressor overcurrent error.
2
9
3 Slave2 outdoor unit inverter compressor overcurrent error.
Table 70: Error Codes, continued.
ERROR CODE TABLES
WARNING
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.