Swing (Setting)
3RLQWQXPEHU
Object name: SwingCommand_XXX (XXX: Indoor address)
Object type: Binary Output
Meaning: This object is to set the air direction of the indoor unit.
Present_Value property:
ACTIVE: Run
INACTIVE: Stop
Swing (Status)
Point number: 10
Object name: SwingStatus_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is to monitor the air direction of the A/C.
Present_Value property:
ACTIVE: Swing_On
INACTIVE: Swing_Off
Fan Speed (Setting)
Point number: 11
Object name: FanSpeedCommand_XXX (XXX: A/C unit address)
Object type: Multistate Output
Meaning: This object is to set the airflow of the A/C.
Present_Value property:
Indoor
Vent
1 : Low
Low
2 : Middle
High
3 : High
Super High
4 : Auto
Auto
Remarks
: The A/C will disregard the command which the object which can't select the
operation mode. Therefore, controlled/monitored system shouldn't use the object
which can't select the operation mode.