Functional Specifications ACP BACnet
Fan Speed (Setting)
Fan Speed (Setting)
Point number: 11
Object name: FanSpeedCommand_XXX (XXX: Indoor/Vent address)
Object type: Multistate Output
Meaning: This object is to set the airflow of the A/C.
Present_Value property:
+PFQQT
8GPV
1 : Low
Low
2 : Middle
High
3 : High
Super High
4 : Auto
Auto
Remarks
: The A/C will disregard the command which the object which can't select the
operation mode.
Therefore, controlled/monitored system shouldn't use the object which can't select
the operation mode.
Fan Speed (Status)
Point number: 12
Object name: FanSpeedStatus_XXX (XXX: Indoor/Vent addresss)
Object type: Multistate Input
Meaning: This object is to monitor the airflow of the A/C.
Present_Value property:
+PFQQT
8GPV
1 : Low
Low
2 : Middle
High
3 : High
Super High
4 : Auto
Auto
Remarks
: Present_value property will be set to "1:Low" as the default result if the property
has not been set in the past.