164
ENGLISH
Functional Specifications ACP BACnet
Heat MIX Damper (Status)
Point number : 53
Object name : MIXDamperHeatStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the MIX heating damper is
set.
3UHVHQW9DOXHSURSHUW\a
Fan OA Damper (Setting)
Point number : 54
Object name : OADamperFANCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the blower damper opening degree of OA.
3UHVHQW9DOXHSURSHUW\a
Fan OA Damper (Status)
Point number : 55
Object name : OADamperFANStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of OA ventilation damper set.
3UHVHQW9DOXHSURSHUW\a
Fan EA Damper (Setting)
Point number : 56
Object name : EADamperFANCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the blower damper opening degree of the EA.
3UHVHQW9DOXHSURSHUW\a
Fan EA Damper (Status)
Point number : 57
Object name : EADamperFANStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the EA ventilation damper set.
3UHVHQW9DOXHSURSHUW\a
Содержание ACP BACnet
Страница 2: ......
Страница 4: ...ii ENGLISH Explanatory Notes ...
Страница 6: ...ENGLISH MEMO ...
Страница 10: ...ENGLISH MEMO ...
Страница 12: ...ENGLISH MEMO ...
Страница 22: ...ENGLISH MEMO ...
Страница 135: ...123 ENGLISH Installing ACP BACnet E may be changed ...
Страница 144: ...ENGLISH MEMO ...
Страница 156: ...144 ENGLISH Functional Specifications ACP BACnet ...
Страница 220: ......