Functional Specifications ACP BACnet
Auto ventilation (Status)
Point number : 27
Object name : AutoVentilStatus_XXX (XXX : AHU address)
Object type : Binary Input
Meaning : This object is used to monitor the presence or absence of the operation of the
automatic ventilatory function.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status
Supply temperature (Status)
Point number : 28
Object name : SupplyTempStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the temperature of the air to be supplied.
Present Value property : -127~127
Outdoor temperature (Status)
3RLQWQXPEHU
Object name : OutdoorTempStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the temperature of the outside air.
Present Value property : -127~127
Mix Temperature (Status)
Point number : 30
Object name : MixTempStatus_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to monitor the temperature of the air that is mixed.
Present Value property : -127~127