Device description
Leuze electronic
ODS 9
17
3.4.3
Output_SSC2 menu
• ODS9LA6: The switching behavior of switching output SSC2 is set to pin 5 in the
Output_SSC2
menu.
• ODS9L6X: The switching behavior of switching output SSC2 is set to pin 2 in the
Output_SSC2
menu.
NOTICE
Ä
The
Output_SSC2
menu is only available for sensors with a second switching output SSC2.
Ä
Designation "SSC" corresponds to designation "Q" previously used for switching outputs.
Level 1
Level 2
Level 3
Description
Default
Output_SSC2 SSC2_SP1_dist.
Upper switching point
Depending on the
device range:
• 100 mm: 75 mm
• 200 mm: 175 mm
• 450 mm: 250 mm
• 650 mm: 350 mm
SSC2_SP2_near
Lower switching point
50 mm
Notice
: For the limit values of the measurement range for your sensor, see chapter 12
SSC2_Hysteresis
Hysteresis
ODS9L1.8…:
10 mm
SSC2_Logic
Behavior of the switching output if an
object is within the taught/configured
switching distance.
• High active: switching output ac-
tive (high)
• Low active: switching output in-
active (low)
High active