Device description
Leuze electronic
ODS 9
18
3.4.4
Analog Output menu
The characteristic output curve of the analog output is set to pin 2 in the
Analog Output
menu.
NOTICE
The
Analog Output
menu is only available for sensors with analog output.
Level 1
Level 2
Level 3
Description
Default
Analog
output
Position Max. Val.
Distance measurement value for
maximum voltage / maximum
current
Upper limit of the
measurement range
Position Min. Val.
Distance measurement value for
minimum voltage / minimum cur-
rent
50 mm
Notice
: For the limit values of the measurement range for your sensor, see chapter 12
Analog range
4 … 20 mA
1 … 10 V
0 … 10 V
Current/voltage range of the
analog output
X
Spreading the characteristic output curve
You can spread the characteristic output curve of the analog output according to your requirements.
Ä
Select the current or voltage range of the analog output.
Ä
Set the distance measurement value that corresponds to the lower limit of the measurement range
(4 mA, 1 V, 0 V).
Ä
Set the distance measurement value that corresponds to the upper limit of the measurement range
(20 mA, 10 V).
It is also possible to invert the working range of the analog output, i.e., the lower limit of the measurement
range is set to a larger value than the upper limit. This creates a descending characteristic output curve.