Starting up the device
Leuze electronic
ODS 9
40
Ä
Position the measurement object at the desired distance.
NOTICE
The teachable area must be located within the measurement range of the sensor.
Ä
Apply the teach signal to the multifunction input (pin 5).
• The duration T of the low level at the teach input determines the teach-in function.
• The teach functions assigned to the time frames are preset and can be queried via IO-Link.
Tab. 7.1:
Assignment of the teach functions
Duration T [ms]
Teach function
Function no.
20 … 80
Object teach of switching output SSC1
14
120 … 180
Window teach (Window) of switching output SSC1
15
220 … 280
Analog teach of the distance value for the smallest analog value
(4 mA, 1 V, 0 V) on pin 2
6
320 … 380
Analog teach of the distance value for the largest analog value
(20 mA, 10 V) on pin 2
7
420 … 480
Preset-Offset calculation:
determination of an offset value so that the preset Preset value is
output as measurement value.
8
520 … 580
Background-Teach_SSC1
16
620 … 680
Setpoint 1-Teach SP1_SSC1
12
720 … 780
Setpoint 2-Teach SP2_SSC1
13
820 … 880
Alternative setpoint 1-Teach SP1a_SSC1
17
920 … 980
Logic of SSC1 to 0 "light switching" Light_SSC1
19
1020 … 1080
Logic of SSC1 to 1 "dark switching" Dark_SSC1
20
1120 … 1180
Toggle logic of SSC1 "light/dark switching"
18
Corresponding IO-Link object
:
Index 140, teach level assignment (Wire Function Array)
Ä
Detection and averaging of measurement values for forming the teach point TP begins with the rising
edge of the input signal.
The parameter or parameters assigned to the time frame for the teach signal is/are updated based on
the teach point.
NOTICE
Ä
With the preset assignment of the teach functions, teaching can only be performed via the
multifunction input in
SinglePoint Object
mode (see chapter 7.1.2 "Setting the switching out-
puts").
Only the upper setpoint SP1 is then shifted, so that the targeted object is just detected
(switching output triggered). More distant objects are no longer detected.
Ä
Other teach modes are possible via IO-Link system commands (see chapter 7.1.5 "Teach-
ing the output functions via the IO-Link system commands").
Ä
Alternatively, the assignment table assignments can also be changed or expanded for ap-
plicative optimization.
NOTICE
A complete process data map of all function indices can be generated via the IODD file. You
can find the IODD file on the Internet at
www.leuze.com
.