Leuze electronic
BCL 558
i
171
TNT
35/7-2
4
V
Writing parameter set
Acknowledgment
negative
’PS=<aa>’
<aa>
Status acknowledgement, unit [dimensionless]
’0’
No difference
’1’
Syntax error
’2’
Impermissible command length
’6’
Impermissible combination, parameter set 1 and parameter set 2
’8’
Invalid parameter set
Command
’PT’
Description
The parameters of the BCL 558
i
are grouped together in a parameter set and perma-
nently stored in memory. There is one parameter set in permanent memory and one
operating parameter set in volatile memory; in addition, there is a default parameter
set (factory parameter set) for initialization. This command can be used to edit the first
two parameter sets (in permanent and volatile memory). A check sum can be used for
reliable parameter transfer.
Parameter
PT<BCC type><PS type><Status><Adr.><P.value adr.>
<P.value adr+1>…[;<Adr.><P.value adr.>][<BCC>]
<BCC type>
Check-digit function during transfer,
unit [dimensionless]
’0’
No check digit
’3’
BCC mode 3
<PS type>
Memory from which the values are to be read,
unit [dimensionless]
’0’
Parameter values stored in the flash memory
’3’
Operating values stored in RAM
<Status>
Mode of parameter processing, without function here, unit [dimen-
sionless]
’0’
No reset after parameter change, no further parameters
’1’
No reset after parameter change, additional parameters follow
’2’
With reset after parameter change, no further parameters
’6’
Set parameters to factory setting, no further parameters
’7’
Set parameters to factory settings, lock all code types; the code-
type setting must follow in the command!
<Adr.>
Relative address of the data within the data set,
’aaaa’
Four-digit, unit [dimensionless]
<P.value>
Parameter value of the -bb- parameter stored at this address. The
parameter set data is converted from HEX format to a 2-byte-ASCII
format for transfer.
<BCC>
Check sum calculated as specified under BCC type
Command
’PD’