Notice!
The respective function as input or output can be set via the display or with the aid of the
webConfig tool!
Described in the following is the external wiring for use as a switching input or output; the
respective function assignments to the switching inputs/outputs can be found in chapter 10.
Function as switching input
Figure 7.3:
Switching input connection diagram SWIO_3 and SWIO_4
If you use a sensor with a standard M12 connector, please note the following:
• Pins 2 and 4 must not be operated as switching outputs if sensors which function as
inputs are also connected to these pins.
If, for example, the inverted sensor output is connected to pin 2, and pin 2 of the bar code
reader is, at the same time, configured as an output (and not as an input), the switching
output malfunctions.
Attention!
The maximum input current must not exceed 8mA!
Function as switching output
Figure 7.4:
Switching output connection diagram SWIO_3 / SWIO_4
Attention!
Each configured switching output is short-circuit proof! Do not load the respective switching
output of the BCL 558
i
with more than 60mA at +10 … +30VDC in normal operation!
Switching input
Switching output
from controller
(deactivated)
Switching input
to controller
Switching output
Switching output
from controller
Switching input
to controller
(deactivated)