Screen 6 - Alarm notification
The following notifications are available on the BIOGAS 3000:
Icon Definition
The alarm is active and the associated relay has been de-energized.
The alarm is active but the channel is within its recovery zone. The
associated relay remains de-energized until the recovery value is met.
This is the latched alarm indicator. This indicates a channel has
alarmed and recovered. During this notification, the relay remains de-
energized until the alarm notification has been acknowledged by the
operator.
The alarm has been silenced by the operator and the associated relay
is energized. The alarm condition on the system remains active in the
background until the recovery condition is met.
Viewing Alarms
5.5.2
To view an alarm, from the ‘Gas Readings Screen’ press the left soft key to go
to