58
Operating Manual
OMBG3000 – Iss.01
© Copyright 2016
Figure 2 - BIOGAS 3000 internal
components for the terminal location and
Wiring Diagram 3 - 4-20mA circuit
for the 4-20mA terminal identification.
Wiring the BIOGAS 3000 to a Current Sinking Input
4.11.2
For this method, the power to the loop is provided by the BIOGAS 3000. The
BIOGAS 3000 sources the current.
Wire the outputs in accordance with
Wiring Diagram 3 - 4-20mA circuit
. For
optimum performance, it is recommended that screened twisted pair cable be
used.
Warning
Only a qualified person should make electrical
connections to the system.
Ensure the power is isolated.
Cable glands should meet the requirements of
Gland Selection and Cord Anchorage
Cable insulation and conductor sizes must meet the
requirements of
Cable Conductor Sizes and Insulation
If using armored cable, the armor must not be used as
the main earth connection for the BIOGAS 3000. If
earthing of the armor is required, this must not be taken
from the BIOGAS 3000.
All cables should be crimped with an appropriate
insulated ferrule for the size of the cable being used. In
addition, the cable insulation must be housed
adequately within the protective sheath of the ferrule.
Terminals that are wired should be tightened to a
minimum of 0.6N
m. Failure to tighten to this
requirement could make the equipment unsafe
resulting in a hazard and invalidate the ATEX/IECEx
certification.