62
Operating Manual
OMBG3000 – Iss.01
© Copyright 2016
The system comes equipped with eight available relays. The relays are volt free
changeover contacts. The maximum rated voltage is 24Vdc.
When being used for alarms and fault notifications the relays are normally
energized (i.e. will de-energize when an alarm condition is triggered). This
means wiring across connections 11 and 12 during a notification will complete
the circuit and de-energize the relay. Refer to
further information.
When being used for sample point indication, catchpot notifications and air
purge notifications, the relays are normally de-energized (i.e. will energize
when the condition is active). This means wiring across connections 11 and 14
during a notification will complete the circuit and energize the relay. Refer to
Wiring Diagram 4 - Relays
Note: For terminal conductor sizes and cable insulation requirements,
please refer to section
Cable Conductor Sizes and Insulation