154
K-CONFIG - Connecting to the Device
10.2.1 Setting K-NET IDs Manually
By default, the K-NET ID of the following devices is set to 2:
•
RC-62
•
RC-62X
•
RC-63A
•
RC-63D
•
RC-63DL
•
RC-63DLN
In order for
K-CONFIG
to recognize the following devices as master room controllers, their K-NET ID must be set to 1
using the
MACH-NUM
Protocol 3000 command. For more information about using Protocol 3000 commands, refer to the
Protocol 3000 User Manual available at:
To manually set the K-NET ID to 1
:
1.
Connect the device to your PC via Ethernet, USB or RS-232.
2.
Using standard telnet communication software, such as Hercules, send the following Protocol 3000 command:
##MACH-NUM 01<CR>
The K-NET ID is set to 1. Some devices may require a restart to complete this operation.
10.3
Firmware Upgrade
Before uploading a new firmware to a room controller device, make certain that the firmware you have
selected matches the connected room controller device. In some cases, it will be possible to upload
firmware that does not match a room controller device, resulting in inoperability of the room controller
device.
Before uploading a new firmware to a room controller device, disconnect it from Site-CTRL and Web
Access.
To load new firmware
:
1.
Check for the latest firmware at:
www.kramerav.com/manual/K-Config 3
2.
Connect the room controller device.
3.
Select
Firmware Update
from the
Device
menu.
The
Firmware Update
window appears: