Page 10
2. The exhaust vent must be at least:
* 4 feet (1.2 m) below
* 4 feet (1.2 m) horizontally from
* 1 foot (0.3m) above
any opening in the building such as doors, windows, ventilation air
intakes, etc.
3. The exhaust vent opening must be a minimum of:
* 12 inches (0.3m) from the ground
* 24 inches (0.61m) from any combustible surface i.e. fence, plant, etc.
* 7 feet (2.1 m) from any public walkway
4. The exhaust air is EXTREMELY HOT. Caution must be taken to avoid
contact with children, people, plants, animals, or any other object that
may be affected by heat. It is recommended to use a vertical pipe to
discharge the hot air at a safe elevation.
5. The vent terminal must have an end cap to protect against down-draft
and back-draft created by severe wind conditions.
5.3 Combustion Air Intake Requirements
There are 2 methods of supplying the heater with combustion air. They are as follows:
1. Room Air: Conventional homes may use room air for combustion
provided APR Part No: CV100 (Check Valve) is installed. For
installations where the exhaust pipe incorporates a minimum 3’ vertical
section immediately adjoining the heater, APR Part No: CV100 (Check
Valve) is optional. In this venting configuration it is highly recom-
mended that the total exhaust vertical rise be longer than the total
horizontal run.
2. Outside Air: All installations can be connected to the exterior of the
building using a non-combustible metal pipe, with a minimum 2 inch
(50mm) internal diameter or by using APR Part No: AK100 (Air
Intake Kit). A larger diameter air intake pipe may be required if the
length of intake exceeds 3’ (1 meter) or has several bends. Use of
plastic pipes are not permitted.
In some installations, outdoor combustion air may be needed to ensure proper perfor-
mance. If your heater burns poorly, experiences roll-out or back-drafts, outside combus-
tion air may be required.
The following restrictions apply to any and all installations:
1. Use of plastic pipes is not permitted under any circumstance.
INSTALL ALL VENTING AT CLEARANCES
SPECIFIED BY THE VENT MANUFACTURER