9.2 Exhaust Vent Requirements
Venting a
KOZI
pellet burner for a mobile home is similar to that of a conventional
home. Please refer to the “Typical Mobile Home Installation Configuration” section for
typical venting configurations. It is highly recommended that a minimum vertical
venting of 3 ft be used (as shown in Figure 13). This will reduce the chance of smoke
spillage into the mobile home in case of a power failure.
9.3 Other Installation Requirements
1. The heater must be securely anchored to the floor of the mobile home.
There are 2 holes located on the base of the stove near the back. Use
two 1/4” lag bolts (not supplied) in these holes to anchor the stove to
the floor of the mobile home.
Figure 12. Anchoring Holes for Mobile Home Installations
2. There must be a non-combustible floor protector placed underneath the
heater and extending a minimum of 6” (150 mm) in front of the heater.
3. This heater can not be installed in any sleeping room of the mobile
home.
4. The heater must be grounded to the steel chassis of the mobile home
(unless this is not required by local code).
9.4 Typical Mobile Home Installation Configuration
The following figures describe some typical installations for mobile homes. Variations of
these are possible. Common sense, safety and compliance with local building codes must
be respected in any variation.
WARNING: DO NOT INSTALL IN A BEDROOM OF A MOBILE HOME
CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOOR, WALL
AND ROOF OF THE MOBILE HOME MUST BE MAINTAINED.