2.2 Free Standing Stove
Minimum clearance must be:
A. Side Wall to Unit
12 inches (300 mm)
B. Back Wall to Unit
1 inch (25 mm)
C. Corner to Unit
1 inch (25 mm)
2.3 Free Standing Installed in an Alcove
Alcove dimensions must be:
Minimum width
48 inches (1220 mm)
Minimum height
48 inches (1220 mm)
Maximum depth
30 inches (760 mm)
2.4 Insert Installed in an Alcove
Alcove dimensions must be:
Minimum width
48 inches (1220 mm)
Minimum height
38 inches (965 mm)
Maximum depth
30 inches (760 mm)
2.5. Insert Installed in a Masonry/Factory Built Fireplace
Minimum clearance must be:
D. Floor protector
6 inches (150 mm)
E. Combustible side wall to unit
12 inches (300 mm)
F. Mantle to unit
13 inches (330 mm)
G. Top facing to unit
13 inches (330 mm)
H. Side facing to unit
12 inches (300 mm)
Please refer to the “Typical Installation Configurations” section and Figure 2 for more
information. Please note the certification label supersedes any information contained in
this manual.
2.6 Other Clearances and Recommendations
1. This heater must be mounted on a non-combustible material, placed
underneath the heater and extending a minimum of 6 inches (150 mm)
in front of the heater.
2. A safety certification label has been attached to either the back of the
heater or inside the hopper lid. A diagram of a sample label is
provided to aid in the identification of the aforementioned clearances.
3. Clearances can ONLY be reduced by means approved by local building
or fire officials in your area.