Page 13
Figure 9A. Factory built zero clearance or
masonry fireplace insert installation
8.
KOZI
KOZI
KOZI
KOZI
KOZI
BayWin
®
Pellet Insert Additional Considerations
The
KOZI
BayWin
®
Pellet Insert can be installed in a masonry or listed factory built
fireplace. The insert’s overall dimensions are 25” (635 mm) in width, 25” (635 mm) in
depth and 23” (585 mm) in height. The minimum opening of a fireplace that is suitable
for a
KOZI
pellet insert is 22” (560 mm) wide, 19.5” (500 mm) high and 16” (410 mm)
deep. The minimum clearances for an insert installed in a masonry or listed factory built
fireplace can be found in the “Clearance to Combustible Walls” section.
Figure 10. Minimum Fireplace opening for the
KOZI
pellet insert.
8.1
KOZI
BayWin
®
Pellet Insert Additional Requirements
When installing and removing a
KOZI
pellet insert in a masonry or listed factory built
fireplace, the following requirements must be met:
1. The room air must be sealed from the exterior. This can be achieved by
sealing the chimney cavity to the liner either at the terminal (see figure
9A) or at the chimney damper (see figure 9B).
2. When installing the insert and its surround, the air flow of the existing
fireplace must not be altered. Make sure no louvers, cooling air or
outlet ports are blocked.
Figure 9B. Factory built zero clearance or
masonry fireplace insert installation