6
.
EtherNet/IP Settings
9
6.2. Global Variable
The Controller treats the data in tag data links as global variables.
The following shows the global variable and related settings.
Name
Data type
Network
Publish
Manifold Solenoid Valve
data allocation
Data size
(bytes)
EIP002_OUT
BOOL[32]
Output
Solenoid output
4
■Relationship between the global variable and solenoid numbers
EIP002_OUT
Array No.
[15] [14] [13] [12] [11] [10] [9] [8] [7] [6] [5] [4] [3] [2] [1] [0]
Solenoid No.
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
Array No.
[31] [30] [29] [28] [27] [26] [25] [24] [23] [22] [21] [20] [19] [18] [17] [16]
Solenoid No.
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
Additional Information
For details on setting the data in tab data links for the Manifold Solenoid Valve, refer to
7
Relationship between I/O data allocation and solenoid valves
of the
EtherNet/IP Compliant
Serial Transmission Compatible Manifold User’s Manual
(BK-HV045).
Additional Information
With Sysmac Studio, two methods can be used to specify an array for a data type.
After specifying, (1) is converted to (2), and the data type is always displayed as (2).
(1)BOOL[32] / (2) ARRAY[0..31] OF BOOL
In this guide, the data type is simplified by displaying BOOL[32].
(The example above means a BOOL data type with thirty-two array elements.)
6.3. Tag Set
The tag set for the originator device to perform tag data links is shown below.
■Output area (Controller to Manifold Solenoid Valve)
Tag set name (Originator variable)
Data size (byte)
EIP002_OUT*
4
Tag name (Global variable)
Data size (byte)
EIP002_OUT
4
*The tag name is used as a tag set name in this guide as only one tag is assigned to the tag
set.
Содержание F Series