7
.
EtherNet/IP Connection Procedure
22
7.3.2. Setting Global Variables
Set a global variable to use for tag data links, and create and export a CSV file in order to use
as a tag with Network Configurator.
1
Double-click
Global Variables
under
Programming
-
Data
in
the Multiview Explorer.
2
The Global Variables Tab Page
is displayed in the Edit Pane.
Click on a space in the
Name
Column to enter a new variable.
Enter
EIP002_OUT
in the
Name
Column.
Enter
BOOL[32]
in the
Data
Type
Column.
After entering, check that the
data type changes to
ARRAY[0..31] OF BOOL.
Select
Output
from the
pull-down list of Network
Publish.
3
Create a tag setting file to use
with Network Configurator, by
following the steps below.
Select
Export Global Variables
-
Network Configurator
from
the Tools Menu while selecting
the row that displays
EIP002_OUT
.