Removal Procedure
The procedure below uses the PFX2011 charge/discharge power supply unit as an
example. The procedure is similar for the PFX2021.
•
Never remove the charge/discharge power supply unit from the unit frame
if the POWER/STANDBY LED is illuminated in green (POWER ON status).
•
Removing and inserting the unit in a short time interval can cause a mal-
function. If you wish to insert the unit that you just removed, wait at least 5
seconds.
1.
Check that the POWER/STANDBY LEDs on the charge/discharge
power supply unit that you wish to remove are illuminated in orange
(STANDBY status).
Fig. 1-5
POWER/STANDBY LED
(PFX2011 Example)
• If the charge/discharge power supply unit that you wish to remove is under the
control of BPChecker2000 (the application software), you must perform unplug
on BPChecker2000 to switch the unit into STANDBY status.
For the procedure in unplugging the unit, see the
BPChecker2000 User's Manual
.
2.
Remove the louver. See Fig. 1-6.
3.
Unfasten the screws that are
fi
xing the unit in place and pull down the
lever towards you.
The unit pops out slightly and the power to the unit is turned off.
The screws that you removed are needed when you install the unit again. Be
sure to store them in a safe place (do not lose them).
4.
Slowly pull the unit out.
When you pull the unit two-thirds of the way out, a lock mechanism is acti-
vated and you can no longer pull the unit out.
CAUTION
Illuminated in green:
POWER ON status
Illuminated in orange: STANDBY status
Remove the unit only when these LEDs
are off or illuminated in orange.