If errors occur, error codes are stored in the error buffer. To read the error code,
execute the
command. To read the error message, execute the
command.
The output of the error codes is in the order that they occurred, and the first four
error codes are stored in the buffer. If no errors occurred, ”0, 0, 0, 0” is returned.
Operation Error
100
Undefined GPIB command.
Send the correct command.
102
Incorrect numeric data syntax.
Correct the data syntax.
103
Incorrect terminator position.
Correct the command syntax. The number of parameters will be
incorrect.
120
Incorrect parameter value.
Correct the parameter value.
121
Channel number must be 1 to 2, or 1 to 8.
Correct the channel number. The channel number must be 1 to 2 for the
Keysight E5262A/E5263A, or 1 to 8 for the Keysight
E5260A/E5270B.
122
Number of channels must be corrected.
Check the MM, FL, CN, CL, IN, DZ, or RZ command, and correct the
number of channels.
123
Compliance must be set correctly.
Incorrect compliance value was set. Set the compliance value correctly.
124
Incorrect range value for this channel.
Check the range value available for the channel, and correct the range
value.
Содержание E5260 Series
Страница 1: ...Keysight Technologies E5260 E5270 Series of Parametric Measurement Solutions Programming Guide...
Страница 3: ...User s Guide B2900 9001x xxxx 201x Edition x...
Страница 13: ...1 Programming Basics...
Страница 63: ...2 Remote Mode Functions...
Страница 108: ...2 46 Keysight E5260 E5270 Programming Guide Edition 4 Remote Mode Functions Initial Settings...
Страница 109: ...3 Programming Examples...
Страница 185: ...4 Command Reference...
Страница 335: ...5 Error Messages...
Страница 349: ......