2-12
BHK-1/2-MG SERIES 030916
FIGURE 2-4. LOCAL SENSING, SLOW MODE SELECTED, GROUNDING NETWORK CONNECTED,
FLOATING OUTPUT (FACTORY DEFAULT CONFIGURATION)
2.7.5.1
LOCAL SENSING/REMOTE SENSING SELECT
Local sensing (factory default configuration) is established by connecting terminals TB1-6
(+S) to TB1-7 (+OUT) and TB1-2 (–OUT) to TB1-3 (–S) (see Figure 2-4). The power supply is
shipped with these connections installed for local sensing.
Remote sensing is established by removing the links between TB1-6, TB1-7 and TB1-2, TB1-3.
The +S and –S lines must be connected at the load (see Figure 2-5).
2.7.5.2
FAST MODE/SLOW MODE SELECT
Fast mode is established when there is no connection between TB1-2 (–OUT) and TB1-1
(–OUT C) (see Figure 2-5). Slow mode (factory default configuration) can be established by
connecting TB1-2 to TB1-1, thus connecting the internal output capacitor to the output (see Fig-
ure 2-4).
2.7.5.3
GROUNDING NETWORK CONFIGURATION
When the output is floating there is a tendency for large changes in output voltage to affect the
digital programming section, possibly resulting in an erroneous output. The parallel RC ground-
ing network is designed to be connected to ground at the output when the output is floating to
ensure that the digital programming section is not adversely affected by the dynamic swing of
the output. The power supply is shipped with the grounding network connected: a connection
Содержание BHK-MG Series
Страница 2: ......
Страница 6: ......
Страница 16: ......
Страница 18: ...xii BHK MG030916 FIGURE 1 1 BHK MG 40W SERIES PROGRAMMABLE POWER SUPPLY...
Страница 24: ...1 6 BHK 1 2 MG OPR 030916 FIGURE 1 2 BHK 40W SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2...
Страница 25: ...BHK 1 2 MG OPR 030916 1 7 FIGURE 1 2 BHK 40W SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 26: ...1 8 BHK 1 2 MG OPR 030916 FIGURE 1 3 RA 24 RACK ADAPTER WITH TWO 1 2 RACK BHK MG 40W UNITS...
Страница 35: ...BHK 1 2 MG SERIES 030916 2 3 FIGURE 2 2 BHK MG SERIES REAR PANEL CONTROLS AND CONNECTIONS...
Страница 100: ...3 54 BHK 1 2 MG 030916 FIGURE 3 20 SERIES AUTOMATIC CONFIGURATION...
Страница 108: ...3 62 BHK 1 2 MG 030916 FIGURE 3 23 PARALLEL AUTOMATIC CONFIGURATION Eo is the output voltage of the power assembly...
Страница 113: ...BHK 1 2 MG 030916 3 67 FIGURE 3 25 PARALLEL MASTER SLAVE CURRENT MODE CONFIGURATION...
Страница 150: ......