3-58
BHK-1/2-MG 030916
3.9.2.2.2 CURRENT MODE OPERATION
When the series combination is operating in current mode (see Figure 3-22), the master is in
current mode and receives current programming commands while output voltage is determined
by the current through the load; the slave is in voltage mode and tracks the master output volt-
age.
FIGURE 3-22. SERIES MASTER-SLAVE (CURRENT MODE) CONFIGURATION