ACD320 user manual
Parameter Description
- 90-
interference.
Function Code
Name
Setting Range
Default
Value
F4.25
Sampling cycle time (T)
0.01
~
100.00s
0.10s
F4.26
PID control discrepancy
limit
0.0
~
100.0%
0.0%
Sampling time (T): is the time to sample the feedback value. In each sampling period the
controller runs one time. The longer the sampling time, the slower the responding.
PID control discrepancy limit: the allowable maximum discrepancy of PIDsystem output
value relative to the closed-loop assigned value.As shown in following diagram,within the
discrepancy limit, PID controller stops adjustment. Properly setting this function code can
improve the accuracy and stability of PIDsystem.
Fig. 6-19 Coincidence relation of discrepancy limit and output frequency
Function Code
Name
Setting Range
Default
Value
F4.27
Feedback disconnection
detecting value
0.0
~
100.0%
0.0%
F4.28
Feedback disconnection
detecting time
0.0
~
3600.0s
1.0s
Feedback disconnected detecting value: this detecting value is relative to the full range
(100%).
The system detects the PID feedback value all the time.When the feedback value is less or
equal to the feedback disconnected detecting value, the system starts to time the detection.When
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......