![K&R ACD320 Series Скачать руководство пользователя страница 85](http://html1.mh-extra.com/html/kandr/acd320-series/acd320-series_user-manual_3099779085.webp)
ACD320 user manual
Parameter Description
- 80-
BIT8: PID setpoint
256
8
BIT9: PID feedback
512
9
BIT10: Input terminal status
1024
10
BIT11: Output terminal status
2048
11
BIT12: AVI value
4096
12
BIT13: ACI value
8192
13
BIT14: Current segment of
multi-speed control
16384
14
BIT15:Torque setting value
32768
15
Stop status display:
Displayed Message
Code
BIT0:Setting frequency
1
BIT1:DC bus voltage
2
BIT2:Input terminal status
4
BIT3:Output terminal status
8
BIT4:PID setpoint
16
BIT5:PID feedback
32
BIT6:AVI value
64
BIT7:ACI value
128
BIT8:Current segment of multi-speed control
256
Option: setting parameter=the sum total of display code for example:
require to display at operation status:Output current,Running speed,Output power
4+16+32=52, then setting F3.05to 52 , its corresponding parameter can be viewed at operation
through pressing button "DATA".
This I/O terminal status is displayed in decimal system,S1 (MO1) corresponding to the
lowest digit.
For instance, input status displays 3 is indicting that terminal S1 and S2 are closed and
others are open.
For details, please see F3.17 and F3.18 description.
Input terminal state display with 10 hexadecimal, as following table:
Input terminal
Effective
Ineffective
MI1
1
0
MI2
2
0
MI3
4
0
MI4
8
0
MI5
16
0
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......