ACD320 user manual
Appendix
- 145-
F7.21
Sleep detection
frequency
0
~
Maximum frequency
0
○
170
F7.22
Sleep detection
delay
0
~
999.9s
0
○
171
F7.23
Revival pressure
1
~
100
0
○
172
F7.24
Revival detection
delay
0
~
999.9s
0
○
173
F7.25
Water-lack detection
delay
0
~
999.9s
0
○
174
F7.28
Selection of
sleeping signal
0
~
2
0
○
177
2.
Detailed description of the parameters
Function code
Name
Setting range
Factory value
F0.08
Acce. Time 1
0.1
~
3600.0s
10.0s
F0.09
Dece. Time 1
0.1
~
3600.0s
10.0s
The acceleration and deceleration time at PID contol is set according to the actual situation.
Function code
Name
Setting range
Factory
value
F3.05
Operation status display
parameter option
1
~
65535
1183
F3.06
Stop
status
display
parameter option
1
~
511
207
F3.07
Operation status display
preferential option.
0
~
15
(
0: It is invalid to
select preferentially
)
0
F3.05=775 is set at PID control, (display the running frequency, setting frequency, output
current , PID
provision
, PID feedback value), F3.06=51 (display setting frequency,
bus-bar
voltage, PID value, PID feedback value), F3.07=8 (display PID value
preferential
), the user can
set accordingly. The detailed explanation of parameters is refered in Chapter 6.
Function code
Name
Setting range
Factory
value
F9.02
Acce. Time 3
0.1
~
3600.0s
445.0s
F9.03
Dece. Time 3
0.1
~
3600.0s
445.0s
The set of accelerating and decelerating time at PID control, this parameter is related to the
set of F4.26 and F7.26, as shown in the following instructions.
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......