Parameter Description
- 61-
F0.13
AVR selection
0:Invalid
1:Valid all the time
2: Invalid during
deceleration
1
AVR means output voltage auto regulation.WhenAVR is invalid, output voltage will change
according to the change of input voltage (or DC bus voltage); WhenAVR is valid,output voltage
will remain constant within output capacity.
Note: When the motor is decelerating to stop, the inverter would decelerate to stop in a
shorter time and not to be over-voltage if automatic voltage stabilization AVR function is closed.
Function Code
Name
Setting Range
Default
Value
F0.14
Start Mode
0:Directstart
1:DC braking first and
then start
0
0: Direct start: start from the starting frequency.
1: DC braking first and then start: First perform DC braking (pay attention to set up
parametersF0.17 and F0.18 ), and then start and run the motor at the start frequency. It is suitable
for small inertia loading which can cause reverse rotation at starting.
Function Code
Name
Setting Range
Default
Value
F0.15
Start frequency
0.50
~
10.00Hz
0.00Hz
F0.16
Hold time of start
frequency
0.0
~
50.0s
0.0s
Setting proper starting frequency can increase the starting torque.Within the hold time of the
starting frequency (F0.16), the inverter output frequency is the starting frequency, and then,from
the starting frequency, running to the target frequency. If the target frequency (frequency
command) is less than the starting frequency, inverter does not operate and is at stand-by state.
The starting frequency value is not restricted by the lower limit frequency.
During FWD/REV switching, the starting frequency is inactive.
Function Code
Name
Setting Range
Default
Value
F0.17
Braking current before
starting
0.0
~
150.0%
0.0%
F0.18
Braking time before
starting
0.0
~
50.0s
0.0s
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......