ACD320 user manual
Parameter Description
- 87-
Fig.6-18 Process PID Functional BlockDiagram
Function Code
Name
Setting Range
Default
Value
F4.18
PID setpoint Sources
Option
0: Given by Keyboard
(F4.19)
1: Given by Analog
Channel AVI
2: Given by Analog
Channel ACI
3: GivenbyRemote
Communication
4: Multi-seg setpoint
0
When frequency source is chosen to be PID, i.e. F0.03 is chosen to be 5, these group
functions are active.
This parameter is to determine the assignment channel of the process PIDtarget value.
The set target value of process PID is a relative value, and the set 100%is corresponding to
the 100% feedback signal of the system being controlled.
The system always performs the calculation according to relative value (0-100%)
Note: If multistage input, it can be accomplished by means of setting F4 group parameters.
Function Code
Name
Setting Range
Default
Value
F4.19
PresetPID setpoint
0.0%
~
100.0%
0.0%
When F4.08=0 is chosen, i.e. the target source is the keyboard, it is required to set this
parameter.
The reference value of this parameter is the system feedback value.
Function Code
Name
Setting Range
Default
Value
F4.20
PID Feedback Sources
Option
0: AVI Feedback
1: ACI Feedback
0
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......