- 144-
Appendix 3 Parameter illustration of the inverter specially used for one driving one
constant pressure water supply
1.
Parameter
illustration of
running mode macroinstruction
Function
code
Name
Setting range
Macroins
truction
setting
Chang
e
Commu
nication
address
Basic parameters
F0.00
Speed control mode
0
~
2
1
×
0
F0.01
Running command
channel
0
~
2
1
×
1
F0.03
Frequency command
selection
0
~
8
5
○
3
F0.05
Running frequency
upper limit
0.00
~
Maximum frequency
49.00
○
5
F0.06
Running frequency
lower limit
0.00
~
F0.05
20.00
○
6
F0.08
Acceleration time 1
0.1
~
3600.0s
10.0s
○
8
F0.09
Deceleration time 1
0.1
~
3600.0s
10.0s
○
9
F2.01
MI1 function
selection
23:One driving two circularly water supply mode
is ineffective
(
switch to manual operation
)
23
×
52
F3.05
Display selection
of running status
parameter
1
~
65535
1183
○
83
F3.06
Display selection
of stopping status
parameter
1
~
511
207
○
84
F3.07
Display of operating
status selected
preferentially
0
~
15
(
0: It is invalid to select preferentially
)
0
○
85
F4.18
PID setpoint Sources
Option
0
:
(
F4.19
)
Digital provision
0
×
115
F4.19
Preset PID setpoint
0.0%
~
100.0%
50.0%
○
116
F4.20
PID Feedback
Sources Option
0
:
AVI effective
0
×
117
F4.21
PID Output
Characteristics Option
0
~
1
0
×
118
F4.22
Proportional gain
(Kp)
0.00
~
100.00
5.00
○
119
F4.23
Integral time (Ti)
0.01
~
10.00s
0.50s
○
120
F4.24
Differential time (Td)
0.00
~
10.00s
0.10s
○
121
F4.25
Sampling cycletime
(T)
0.01
~
100.00s
0.10s
○
122
F4.26
PID control
discrepancy limit
0.0
~
100.0%
5.0%
○
123
F4.27
Feedback
disconnection
detecting value
0.0
~
100.0%
0.0%
○
124
F4.28
Feedback
disconnection
detecting time
0.0
~
3600.0s
1.0s
○
125
F9.02
Acce. time 3
0.0
~
3600.0s
445.0s
○
202
F9.03
Dece. time 3
0.0
~
3600.0s
445.0s
○
203
F7.26
PID adjusting range
0
~
50.0
5.0
○
175
Parameters when sleeping and revival and lack of water detection are needed
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......