ACD320user manual
Function parameters list
- 45-
F3.11
The
fault
before
previous fault type
0
:
No fault
1: IGBT module protection
2: Acceleration over-current
3: Deceleration over-current
4: Constant speed over-current
5: Acceleration over-voltage
6: Deceleration over-voltage
7: Constant speed over-voltage
8: Control power fault
(
Stop over-voltage
)
9: Operation under-voltage fault
10: Inverter overload
11: Motor overload
12: Input side phase failure
13: Output side phase failure
14: Inverter overhea
15: External fault
16:RS485 communication fault
17:Reserved
18: Current detect error
19: Motor self-learning error
20:Reserved
21: EEPROM operation error
22: hardware fault
23: short-current fault
25: PID feedback disconnect er ror
26:Water-lack protection failure
27
:
the inverter operation time reached
0
*
89
F3.12
Previous fault type
0
*
90
F3.13
Current fault type
0
*
91
F3.14
Operating
frequency at current
fault
0.00
~
600.00Hz
0
.
00Hz
*
92
F3.15
Output amperage at
current faul t
0.0
~
2000.0A
0.0A
*
93
F3.16
Bus voltage at
current fault
0.0
~
1000.0V
0.0V
*
94
F3.17
Reserved
0
○
95
F3.18
Reserved
0
○
96
F4 Application Function Parameters
F4.00
ACCELTime2
0.1
~
3600.0s
10.0s
○
97
F4.01
DECELTime2
0.1
~
3600.0s
10.0s
○
98
F4.02
Frequency of Jog
running
0.00
~
F0.04
5.00Hz
○
99
F4.03
The acceleration
time of JOG
running
0.1
~
3600.0s
10.0s
○
100
Содержание ACD320 Series
Страница 1: ......
Страница 26: ...ACD320user manual Installation and wiring 21 11 30KW...
Страница 120: ...ACD320user manual Fault Diagnosis and countermeasures 115 1 Inverting module protection U 01...
Страница 124: ...ACD320user manual Fault Diagnosis and countermeasures 119 8 Under voltage U 09 9 InverterOver Load U 10...
Страница 126: ...ACD320user manual Fault Diagnosis and countermeasures 121 13 Inverting Module Over Heat U 14 14 External Failure U 15...
Страница 160: ......