Commis s ioning and configuration
KNX Sonos -Gateway
MR-SONOS-REG
© 2019 Albrecht J ung GmbH & Co. KG
p. 50 / 118
8.1.1
LEDs when the device starts up
After the power s upply (DC 24 V on the yellow-white power connection terminal) is s witched on or after power
returns , the device indicates its s tatus us ing the following LED combinations :
Table 9: Status of the device – Device starting up
APP
COM
Description
Correct operation
(off)
(yellow)
Device s tarting up.
(green)
(yellow)
Device booted up and ready for operation.
Error
(off)
(off)
No power s upply.
Check the connections and the power s upply.
….. ….. ….. …..
(off)…..(green)…..(off)…..(green)…..
Slow flas hing (about 1 Hz)
(yellow)
The device is fully s tarted up but is not yet configured.
The s ys tem is configured S mode.
Configure the device in the ETS.
….. ….. ….. …..
(off)…..(green)…..(off)…..(green)…..
Slow flas hing (about 1 Hz)
(off)
The device is fully s tarted up but is not yet configured.
The s ys tem is configured S mode.
Configure the device in the ETS.
Connection to KNX is interrupted.
Check whether the KNX and voltage connections
are mixed up.
Check the bus connection.
Check whether the power s upply is correctly connect-
ed.
. . . . . .
(off).(green).(off).(green).(off).(green).
Rapid flas hing
(off)
The firmware cannot be s tarted.
Pleas e contact s upport.
►
Contacting Support, p.
Fehler! Textmarke nicht
definiert.
….. ….. ….. …..
….. ….. ….. …..
(off)…..(green)…..(off)…..(green)…..
(yellow)…..(off)…..(yellow)…..(off)…..
Slow flas hing (about 1 Hz) in an alternating pattern
The newly loaded firmware cannot be started. The
s ys tem is trying to activate the previous firmware
(invalid firmware).
Pleas e contact s upport.
►
Contacting Support, p.
Fehler! Textmarke nicht
definiert.