SECTION 2 - OPTIVIEW OPERATION
Pressure
This display indicates the pressure in the purge tank.
Exhaust Count
Exhaust count is only displayed after an initial 60-min-
ute bypass occurs at chiller start-up. Displays the num-
ber of purge exhausts that have occurred within the last
0 to 60 minutes, as displayed in the exhaust window.
When the purge unit reaches the excess purge threshold
or the chiller shuts down, the count display is frozen.
The count will be reset when the chiller starts again.
Exhaust Window
Displayed as 0 to 60 minutes. After a 60 minute by-
pass at chiller start, the exhaust window times from 0
to 60 minutes. During this period, purge exhausts are
counted and the exhaust count displayed is that which
has occurred in the last number of minutes displayed in
the exhaust window. After the exhaust window reaches
60, the purge exhausts that occurred in the oldest min-
ute are discarded from the exhaust count and exhausts
from the most recent minute are shifted in, providing a
rolling count of purge exhausts that occurred in the last
60 minutes. The count remains at 60 until the chiller is
restarted, whereupon the count is reset to 0.
PROGRAMMABLE
High Efficiency Purge System (Enabled /
Disabled)
Access Level Required: SERVICE
Selects the appropriate control and purge exhaust
thresholds for the purge system installed on the chiller.
High efficiency (pump assisted) purge systems exhaust
above 90.0 PSIA. Non pump-assisted purge systems
exhaust above 34.7 PSIA. Trane chillers equipped with
a TurboGuard II must be set to “Enabled”.
Maximum Purges/Hour
Access Level Required: OPERATOR/SERVICE
Allows the user to define the number of purge air ex-
hausts permitted before a warning for excess purge is
displayed. With “Operator” access level, the value can
be programmed over a range of 10 to 30 Purges/Hour.
The “Service” access level allows this setpoint to be
programmed over a range of 1 to 30 Purges/Hour.
Change Setpoint
Access Level Required: VIEW
Allows user to enter login password to change purge
settings. This button is only present at the “View” ac-
cess level.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Condenser
Access Level Required: VIEW
Returns the display to the Condenser screen.