SECTION 2 - OPTIVIEW OPERATION
SLOT#
DESCRIPTION
2866
Filter: Phase Rotation
2867
Filter: Motor HP
2868
Filter: Supply kVA
2869
Filter: Total Power Factor
2870
Filter: DC Bus Voltage
2871
Filter: Heatsink Temperature
2872
Filter: L1 - L2 RMS Voltage
2873
Filter: L2 - L3 RMS Voltage
2874
Filter: L3 - L1 RMS Voltage
2875
Filter: L1 - N Peak Voltage
2876
Filter: L2 - N Peak Voltage
2877
Filter: L3 - N Peak Voltage
2878
Filter: L1 Total Harmonic Distortion
2879
Filter: L2 Total Harmonic Distortion
2880
Filter: L3 Total Harmonic Distortion
2881
Filter: L1 RMS Filter Current
2882
Filter: L2 RMS Filter Current
2883
Filter: L3 RMS Filter Current
2884
Filter: L1 RMS Supply Current
2885
Filter: L2 RMS Supply Current
2886
Filter: L3 RMS Supply Current
2887
Filter: L1 Total Demand Distortion
2888
Filter: L2 Total Demand Distortion
2889
Filter: L3 Total Demand Distortion
2890
Filter: Maximum Total Harmonic Distortion
2891
Filter: Maximum Total Demand Distortion
8192
Oil: Pump Pressure
8193
Oil: Sump Pressure
8205
Refrigerant Level: Is Control Enabled
8206
Refrigerant Level: Position
8207
Refrigerant Level: Is Valve Closing
8208
Refrigerant Level: Is Valve Opening
8209
Refrigerant Level: Control Mode
8212
Refrigerant Level: Target Setpoint
8213
Refrigerant Level: Setpoint
8214
Refrigerant Level: Period
8215
Refrigerant Level: Proportional Limit Close
8216
Refrigerant Level: Proportional Limit Open
8217
Refrigerant Level: Rate Limit Close
8218
Refrigerant Level: Rate Limit Open
12288
Purge: Pressure
12289
Purge: Is Air Purge Valve Closed
12290
Purge: Is Oil Purge Valve Closed
12291
Purge: Is Bottom Float Switch Closed
12292
Purge: Is Top Float Switch Closed
SLOT#
DESCRIPTION
12293
Purge: Exhaust Count
12294
Purge: Window Time
12295
Purge: Is High Efficiency Enabled
12296
Purge: Maximum Purges Per Hour
17958
Winding Phase A1 Temperature
17959
Winding Phase A2 Temperature
17960
Winding Phase B1 Temperature
17961
Winding Phase B2 Temperature
17962
Winding Phase C1 Temperature
17963
Winding Phase C2 Temperature
17964
Bearing 1 Temperature
17965
Bearing 2 Temperature