JOHNSON CONTROLS
134
FORM 160.10-O1
ISSUE DATE: 4/27/2018
APPENDIX B - PROGRAMMABLE SETPOINT VALUES
COMPRESSOR SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Vent Line Off State
Service
De-Energized
Energized
De-Energized
HOT GAS BYPASS SCREEN (COMPRESSOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Close Percentage
Service
5 %
15 %
5 %
Hold Period
Service
30 Min
120 Min
30 Min
Surge Sensitivity
Service
0.1
1.3
0.3
Minimum Load
Service
0 °F
4 °F
0°F
VSD CALIBRATION SCREEN (COMPRESSOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Increment Amount
Service
0.1 Hz
10.0 Hz
1 Hz
SURGE PROTECTION SCREEN (COMPRESSOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Shutdown
Service
Disabled
Enabled
Enabled
Extended Run
Service
Disabled
Enabled
Disabled
Count Window
Service
1 Min
5 Min
3 Min
Count Limit
Service
4
20
15
Surge Sensitivity
Service
0.3
1.3
0.3
OIL SUMP SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Manual Pump
Operator
Disabled
Enabled
Disabled
Low Pressure Limit
Service
10 PSID
40 PSID
25 PSID
Prelube Time
Service
15 Seconds
60 Seconds
30 Seconds
Coastdown Time
Service
150 Seconds
600 Seconds
150 Seconds
Heater Setpoint
Service
125 °F
155 °F
140 °F
ELECTROMECHANICAL STARTER SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
TABLE 13 -
PROGRAMMABLE SETPOINT VALUES (CONT’D)
Содержание YORK OPTIVIEW CONTROL CENTER
Страница 12: ...JOHNSON CONTROLS 12 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...JOHNSON CONTROLS 118 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 140: ...JOHNSON CONTROLS 140 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...