JOHNSON CONTROLS
99
SECTION 2 - OPTIVIEW OPERATION
FORM 160.10-O1
ISSUE DATE: 4/27/2018
2
SLOT#
DESCRIPTION
2049
Leaving Condenser Liquid: Is Flow Switch
Closed
2050
Leaving Condenser Liquid: Is Pump On
2051
Return Condenser Liquid: Temperature
2052
Condenser: Pressure
2053
Condenser: Saturation Temperature
2054
Condenser: Small Temperature Difference
2057
Condenser: Is High Pressure Switch Closed
2058
Condenser: High Pressure Warning Threshold
2059
SubCooling: Temperature
2060
Drop Leg Refrigerant: Is Sensor Present
2061
Drop Leg Refrigerant: Temperature
2062
Vent Line Solenoid: Is Solenoid Installed
2063
Vent Line Solenoid: Is Solenoid On
2304
Motor: Starter Type
2305
Motor: Is Motor Starter On
2306
Motor: Current %FLA
2307
Motor: Is Motor Controller Switch Open
2308
Motor: Current Limit Local Setpoint
2309
Motor: Current Limit Remote Analog Setpoint
2310
Motor: Current Limit Remote ISN Setpoint
2311
Motor: Current Limit Remote Modem Setpoint
2312
Motor: Current Limit Selected Setpoint
2313
Motor: Pulldown Demand Time Remaining
2314
Motor: Pulldown Demand Limit Setpoint
2315
Motor: Pulldown Demand Time Setpoint
2316
Motor: Anti-Recycle Time Remaining
2317
Motor: Current Limit Remote Digital Setpoint
(Mod “B” Solid State Starters)
2570
LcSss: Input Power
2571
LcSss: Kilowatt Hours
2572
LcSss: Phase A Current
2573
LcSss: Phase B Current
2574
LcSss: Phase C Current
2575
LcSss: Phase A Voltage
2576
LcSss: Phase B Voltage
2577
LcSss: Phase C Voltage
2578
LcSss: Phase A Temperature
2579
LcSss: Phase B Temperature
2580
LcSss: Phase C Temperature
2581
LcSss: Starter Model
2582
LcSss: Full Load Amps
2583
LcSss: Voltage Range
2584
LcSss: Starting Current
2585
LcSss: Is Serial Communications OK
2586
LcSss: Panel to Sss Comm Errors
SLOT#
DESCRIPTION
2587
LcSss: Sss to Panel Comm Errors
2816
VSD: Motor HP
2817
VSD: 100% Full Load Amps
2818
VSD: Input Power
2819
VSD: Kilowatt Hours
2820
VSD: DC Bus Voltage
2821
VSD: DC Inverter Link Current
2822
VSD: Output Frequency
2823
VSD: Output Voltage
2824
VSD: Phase A Current
2825
VSD: Phase B Current
2826
VSD: Phase C Current
2827
VSD: Is Precharge Relay On
2828
VSD: Is Trigger SCR On
2829
VSD: Is Water Pump On
2830
VSD: Control Mode
2831
VSD: Command Frequency
2832
VSD: Manual Frequency Increment
2833
VSD: Internal Ambient Temperature
2834
VSD: Converter Heatsink Temperature
2835
VSD: Phase A Heatsink Temperature
2836
VSD: Phase B Heatsink Temperature
2837
VSD: Phase C Heatsink Temperature
2838
VSD: Is Communications OK
2839
VSD: Panel to ACC Comms Error Count
2840
VSD: ACC to Panel Comms Error Count
2841
VSD: ACC to VSD Comms Error Count
2842
VSD: VSD to ACC Comms Error Count
2843
VSD: VSD to Filter Comms Error Count
2844
VSD: Filter to ACC Comms Error Count
2845
ACC: Delta P/P
2846
ACC: Stability Limit
2847
ACC: Surge Margin
2848
ACC: Manual Surge Command
2849
ACC: Surge Map Count
2850
ACC: Surge Type
2857
ACC: Surge Map Point Count
2858
ACC: Surge Map Delta P/P
2859
ACC: Surge Map Output Frequency
2860
ACC: Surge Map PRV Position
2861
Filter: Is Filter Installed
2862
Filter: Is Operation Inhibited
2863
Filter: Is Filter Running
2864
Filter: Is Precharge Contactor Closed
2865
Filter: Is Supply Contactor Closed