SECTION 2 - OPTIVIEW OPERATION
FORM 160.10-O1
ISSUE DATE: 4/27/2018
2
Network) mode, or programmed locally at the control
center in local mode.
Pulldown Demand Time Left (Not Shown)
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Operating Mode (Run / Stop)
This indicates the mode of operation for the chiller har-
monic filter.
VSD Model
Access Level Required: SERVICE
Displays the horsepower configuration of the variable
speed drive control reported by the VSD to the OptiV-
iew control panel.
DC Bus Voltage
Displays the DC bus voltage as measured by the Har-
monic Filter.
OVERVIEW
This screen displays more detailed information per-
taining to the IEEE-519 Harmonic Filter. This screen
is only available on the OptiView panel if the harmonic
filter is installed.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to “RUN”.
(Motor Current) % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. For the variable speed drive
this is the data returned by the VSD logic board.
Current Limit Setpoint
Displays the current limit setpoint programmed by
the operator. This value could come from a 0-20mA,
4-20mA, 0-10VDC or 2-10VDC input in analog re-
mote mode, PWM signal in digital remote mode,
MicroGateway interface in ISN (Integrated Systems
HARMONIC FILTER DETAILS SCREEN 2
VSD WITH PART NUMBER 371-02767-XXX (60 HZ) OR 371-03700-XXX (50 HZ)
00664VIP
FIGURE 22 -
HARMONIC FILTER DETAILS SCREEN 2