APPENDIX B - PROGRAMMABLE SETPOINT VALUES
HARMONIC FILTER DETAILS SCREEN (HARMONIC FILTER SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
MOTOR TEMPERATURE SCREEN (MOTOR SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Winding Sensor Mode
Service
None, Analog, Digital, Analog and
Digital
None
Winding Cutout
Service
150 °F
300 °F
265 °F
Bearing Sensor Mode
Service
None, Analog, Digital, Analog and
Digital
None
Bearing Cutout
Service
100 °F
180 °F
180 °F
Motor Cooling Pump
Service
Disabled
Enabled
Disabled
Motor Cooling Pump Mode
Service
Automatic
Manual
Automatic
Phase A (Active Sensor)
Service
None, A1, A2, A1 and A2
None
Phase B (Active Sensor)
Service
None, B1, B2, B1 and B2
None
Phase C (Active Sensor)
Service
None, C1, C2, C1 and C2
None
Bearing (Active Sensor)
Service
None, Sensor 1, Sensor 2,
Sensor 1 and 2
None
SETPOINTS SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Leaving Chilled Liquid Temperature - Setpoint
Operator
38.0 °F - Water
36.0 °F - Sm Frz
10.0 °F - Brine
70.0 °F
45.0 °F
Local Leaving Chilled Liquid Temperature - Range
Operator
10.0 °F
20.0 °F
20.0 °F
LCHLT Cycling Offset - Shutdown
Operator
1.0°F
64.0 °F
4.0 °F or high-
est allowed
value, which
-
ever is lower.
LCHLT Cycling Offset - Restart
Operator
0.0 °F
70.0 °F
0.0 °F
Remote Analog Input Range
Operator
0 - 10 VDC
2 - 10 VDC
0 - 10 VDC
Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
TABLE 13 -
PROGRAMMABLE SETPOINT VALUES (CONT’D)
Содержание YORK OPTIVIEW CONTROL CENTER
Страница 12: ...JOHNSON CONTROLS 12 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...JOHNSON CONTROLS 118 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 140: ...JOHNSON CONTROLS 140 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...