JOHNSON CONTROLS
130
FORM 160.10-O1
ISSUE DATE: 4/27/2018
SECTION 4 - PRINTERS
[Not if Motor Type is not Mod B SSS]
Liquid-Cooled Solid State Starter
-----------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
Starter Model
= 26L
Voltage Range
= 440 - 480
Full Load Amps
= 275 A
Starting Current
= 1150 A
Open SCR
= Enabled
Shorted SCR
= Disabled
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
-----------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
Motor HP
= 351 HP
Power Line Frequency
= 60 Hz
[Skip the following section if Motor Type is not VSD]
Harmonic Filter Data
-----------------------------------------------------
Filter Operation
= Enabled
Motor HP
= 351 HP
[Skip the following section if Motor Type is not VSD]
Adaptive Capacity Control
-----------------------------------------------------
Surge Margin Adjust
= 0 Hz
Stability Limit
= 4500
FIGURE 52 -
SAMPLE PRINTOUT (SETPOINTS)
(CONT’D)