JOHNSON CONTROLS
46
FORM 160.10-O1
ISSUE DATE: 4/27/2018
SECTION 2 - OPTIVIEW OPERATION
used to provide energy savings following chiller start-
up and is adjustable from 30 to 100%, with 100% as
the default setting.
Pulldown Demand Time
Access Level Required: OPERATOR
This setpoint programs the period of time the pulldown
demand limit will be in effect after the chiller starts.
The pulldown demand time is adjustable from 0 to 255
minutes, with 0 minutes as the default.
Motor Cooling Pump
Access Level Required: Service
This enables motor cooling pump when one of the
motor winding temperatures exceed the setpoint pro-
grammed on the Motor Temperature Screen. The mo-
tor cooling pump can only operate when the machine
is running.
Change Setpoint
Access Level Required: VIEW
Allows user to enter login password to change motor
settings. This button is only present at the “View” ac-
cess level.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Motor Temperature
Access Level Required: VIEW
Advances the display to the Motor Temperature screen.