JOHNSON CONTROLS
44
FORM 160.10-O1
ISSUE DATE: 4/27/2018
SECTION 2 - OPTIVIEW OPERATION
PROGRAMMABLE
Manual Pump (Enabled/Disabled)
Access Level Required: Operator
This key allows the oil pump to be manually activated.
The oil pump will run for ten (10) minutes when man-
ual pump is “Enabled”. After ten minutes, the display
will revert to “Disabled”. If a longer run time is desired
the manual pump must be enabled again when the time
has elapsed. Manual oil pump control is only available
when the chiller is stopped. The Manual Pump key is
not displayed during system prelube, system run and
system coastdown.
Low Pressure Limit
Access Level Required: Service
Allows the minimum oil pressure the system is permit-
ted to operated at to be adjusted. This setting can be
adjusted from 10.0 PSID to 40.0 PSID, with 25.0 PSID
as the default setting.
Prelube Time
Access Level Required: Service
Allows the system prelube time to be adjusted from 15
seconds to 60 seconds. The default setting is 30 sec-
onds.
Coastdown Time
Access Level Required: Service
Allows the system coastdown time to be adjusted from
150 seconds to 600 seconds. The default setting is 150
seconds.
Recycle Time
Access Level Required: Service
This key enables standby lubrication by setting how of-
ten you want the oil pump to come on when the chiller
has been offline. If the chiller runs before the time pe-
riod elapses then the timer will be reset. The time is
between 2 hours and 12 hours in 2 hour increments.
By selecting Disabled it will prevent the oil pump from
running when the chiller is off for an extended period
of time.
Change Setpoint
Access Level Required: VIEW
Allows the login password to be entered to change
oil pump settings. This button is only present at the
“View” access level.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.