5 Initial commissioning
In delivered condition, the HMI may already include a visualization application
with an
*.iop
file stored to the folder
Data
.
This is also the case, if the CAN bus node ID must be set.
Result:
The HMI will not display your visualization application.
Remedy:
Step
Action
1
If ...
... then ...
... the file
\App\visual.iop
or
\Data\visual.iop
exists,
... delete or rename this file.
2
If ...
... then ...
... the file
\App\JetViewERS.cfg
exists, ...
... delete or rename this file.
The visualization application developed for the ER-STX-CE platform is
displayed.
Initial commissioning in JetSym
(see page 91)
IOP file as visualization
application on the HMI
Related topics