Jetter AG
115
JVM-407B
CANopen® STX API
After successfully calling up the function, the Busy parameter is set to
SDOACCESS_INUSE. With an error in transmission, Busy is set to
SDOACCESS_ERROR. With a successful transmission, the function returns
the number of bytes transmitted.
With an error in transmission, Busy returns an error code. The following error
codes are available:
SDOACCESS_STILLUSED
Another task is communicating with the same node ID.
SDOACCESS_TIMEOUT
The task has been timed out because the device with the specified node ID is
not responding.
If the specified node ID does not respond within 1 second, the timeout bit is
set.
SDOACCESS_ILLCMD
The response to the request is invalid.
SDOACCESS_ABORT
Access to the device with the specified node ID was aborted.
SDOACCESS_SYSERROR
General internal error
The following macros have been defined in connection with this function:
SDOACCESS_FINISHED (busy)
This macro checks whether communication has finished.
SDOACCESS_ERROR (busy)
This macro checks whether an error has occurred.
Busy
"Busy" error codes
Macro definitions
Содержание JVM-407B-HMI
Страница 1: ...User Manual JVM 407B HMI 60879892 We automate your success...
Страница 14: ......
Страница 26: ...26 Jetter AG 2 Product description and design Rear view...
Страница 34: ......
Страница 80: ......
Страница 98: ...98 Jetter AG 5 Initial commissioning Initial commissioning in JetViewSoft see page 86 Related topics...
Страница 106: ......
Страница 144: ......
Страница 168: ......
Страница 178: ......
Страница 182: ......
Страница 196: ...196 Jetter AG 10 Programming If Merker1 Then Inc Status_LEDs Delay T 100ms End_If End_Loop End_Task...
Страница 220: ...220 Jetter AG 10 Programming Topic Page Programming 221 Registers 233 Sample programs 238 Contents...
Страница 258: ......
Страница 268: ......
Страница 274: ......
Страница 294: ...294 Jetter AG Appendix Rear view...
Страница 299: ......