Doc ref. :
332190D –
EN
28.04.2014
Page 44 / 49
11 Procedures
11.1 Accessing a machine area in « monitoring - diagnostic » mode
The enabling handle is on its charger and the machine is in service. The green indicator light on the indicator light
column is on steady.
Remove the handle from its charger.
The orange indicator light on the indicator light column flashes (duration programmed by «
A
» selectors on
safety receiver).
Activate the trigger on the handle within the time delay selected.
The green and orange indicator lights on the indicator light column come on steady.
Area entrance request by a gate :
Without releasing the trigger, transmit a request for entrance into the area through the gate (by pressing
B1
or
B2
). The orange indicator light on the indicator light column flashes (duration programmed by «
A
» selectors
on receiver).
Open the gate and close it within the muting time programmed for the gate. (Duration programmed by “
A
”
selectors on receiver).
Once the door is crossed and closed, orange and green lights on the indicator light column come on steady
again. The trigger on the handle will be maintained throughout the “monitoring – diagnostic” phase of the
equipment.
Area exit request by a gate :
Without releasing the trigger, transmit a request to «exit the area» through the gate (by pressing
B1
or
B2
).
The orange indicator light on the indicator light column flashes and the green indicator light remains on steady.
Pass through the gate and close it within the gate muting time programmed.
Without releasing the trigger, present the handle in front of the charger.
The orange indicator light on the indicator light column flashes.
Release the trigger on the handle.
Place the handle on its charger.
The orange indicator light on the indicator light column goes off and the green indicator light remains on
steady.
Note:
This procedure is the same whether the area is protected by a
safety light barrier
.