5.4.8 Wiring of an equipment without area access protection
If the equipment does not have a peripheral protection system with a machine area access feature, you must connect
jumpers across the machine area access monitoring inputs, S21-S22 and S23-S24.
5.4.9 Wiring of “handle on charger” detection function
This function must be wired to inhibit the enabling handle when it is not used. Once an intervention on a machine is
completed, the operator must place the enabling handle on its charger in order to allow the equipment to operate
again in automatic mode.
The two outputs, S1 and S2, must be connected to the receiver.
- These should be connected to inputs S31-S32 and S33-S34 when the receiver is not used to manage
machine area access (see diagram 1)
- These must be connected in series to inputs S31-S32 when the receiver is used to manage machine area
access. The passage request must be connected on input S33 (see diagram 2)
- Output 17 gives the “handle on charger” status (output active = handle present).
Diagram 1 :
Wiring for configuration
without
machine area access