5.11 Receiver wiring examples
5.11.1 Wiring diagram for configuration without access control
The receiver does not manage machine area access.
In addition to the radio input associated to the enabling handle, an emergency stop can be wired to the receiver.
Otherwise,
you must wire 2 jumpers across S11-S12 and S13-S14.
To select the correct application program, refer to the
« receiver configuration » section.
5.11.2 Wiring diagram for configuration with access control by gate
Reminder :
The handle can only be configured in « 4 control buttons » mode.
To monitor access to the machine area, it is necessary to wire two NO contacts on the gate on inputs S21-S22 and S23-S24.
These contacts will be inhibited to allow the operator to access the machine area without deactivating the machine
emergency stop system.
In the diagram below, output 27, associated to button B1 of the handle, is wired to output S34.
For a machine access request using your right hand (pressing B2 instead of B1), be sure to connect output 37 (instead of
27) to input S34.