background image

Page 7 

ENGLISH

  

 

Jandy

®

 Pro Series, Hi-E2

®

 and Hi-E2R Gas-Fired Heater   

|

   Installation & Operation Manual

Figure 4.  Vent collar assembly for indoor installation.

Figure 3.  Removal of outdoor exhaust grille.

The necessary vent collar, gasket and screws are shipped 

packaged within the heater. The conversion can be done 

quite simply as follows. See Figures 3 and 4:

1. 

Remove the vent exhaust grille by removing the 

four (4) screws which retain it. The grille, its 

gasket, and the screws may be discarded.

2. 

Place the vent collar gasket on the top of the 

heater aligning its center hole and screw holes 

with those in the top of the heater.

3. 

Place the vent collar over the gasket and fasten 

it in place with the screws and lockwashers 

provided. Be sure that all components are 

properly aligned. Screws must be tightened 

enough to assure a sealed joint without deforming 

the vent collar.

2.7.2  Combustion Air Requirements for One-Pipe 

Installation

One-pipe indoor installations must have specific 

provisions for supply of combustion and ventilation air 

to the room in which the heater is located. Two (2) air 

openings must be provided — one (1) near the ceiling 

and one (1) near the floor. When air is provided directly 

through an outside wall, each opening must have at least 

1 square inch (6.5 square cm) of area per 4000 BTU/h of 

heater input. When air is provided indirectly through ducts 

from the outside, the openings and passages must have 

at least 1 square inch of area per 2000 BTU/h of heater 

input. These requirements are interpreted in Table 2.

Table 2. 

Required Net Free Area of Openings for 

Combustion and Ventilation Air.

Model

 

Required net free area in square  

inches (sq. cm) for each of 2 openings -  

one (1) near ceiling and one (1) near floor

Directly 

Through an 

Exterior Wall

Through Horizontal 

Ducts

350

88 (570)

175 (1130)

Note that the numbers indicate the 

net free area

 — 

after allowing for the blockage of grille bars, etc. See 

applicable local codes and the previously-cited national 

codes for details. Even though codes may permit it, 

Zodiac

®

 does not recommend installations with only 

“infiltration” as the means for provision of combustion air.
See Section 2.7.3.3 for vent pipe sizing.

 WARNING

Do not store any chemicals, cleaners, or other corrosive 

material near combustion air openings or in the 

room. Avoid locating appliance vents in the vicinity of 

combustion air openings. Failure to prevent corrosive 

materials from mixing with combustion air can result in 

reduced heater life and unsafe heater operation.

2.7.3  Two-Pipe Installation (Direct Vent)

This section specifies installation requirements 

for combustion air and vent piping for “two pipe” 

installations. A two-pipe system provides isolation of the 

Hi-E

2

 combustion system from the space in which the 

heater is installed. It has not only a vent pipe, but also 

a combustion air pipe to provide air directly from the 

outdoors. Research studies have shown that contaminants 

which may corrode internal heater parts are typically at 

much lower levels in outdoor air than in air from indoors.

2.7.3.1  Connection of Combustion Air Pipe

A collar for combustion air pipe connection is provided in 

the heater at the inlet of the filter box. As shown in Figure 

5, the combustion air pipe is routed through the side of the 

heater to the filter box connection. Remove the cover plate 

from the left side panel to provide access for the air pipe.

Содержание HI-E2

Страница 1: ...ion and or operation can create carbon monoxide gas and flue gases which can cause serious injury property damage or death For indoor installations as an additional measure of safety Zodiac Pool Syste...

Страница 2: ......

Страница 3: ...tion 17 2 12 2 Start up 17 2 12 3 Condensate 17 2 12 4 Gas Pressure 18 2 12 5 Adjustment of Water Pressure Switch 18 2 12 6 Water Temperature Rise 19 Section 3 Operating Instructions 19 3 1 Start Up P...

Страница 4: ...arranty The Hi E2 is sold with a limited factory warranty A copy of the warranty is included in a plastic bag inside the heater The warranty does not cover damage caused by improper installation opera...

Страница 5: ...building codes for additional requirements CAUTION When pool equipment is located below the pool surface a leak from any component can cause large scale water loss or flooding Zodiac Pool Systems Inc...

Страница 6: ...of the heater The correct size drill bit is usually provided with the concrete screws when purchased Place a screw in each of the holes and fasten the heater to the equipment pad see Figure 2 Do not o...

Страница 7: ...and Ventilation Air Model Required net free area in square inches sq cm for each of 2 openings one 1 near ceiling and one 1 near floor Directly Through an Exterior Wall Through Horizontal Ducts 350 88...

Страница 8: ...boratory NRTL as being compliant with the applicable requirements of the Underwriters Laboratories UL standard for safety for Venting Systems for Gas Burning Appliances Categories II III and IV ANSI U...

Страница 9: ...on inlets etc In the United States this distance must be at least 4 feet 1 21 m In Canada it must be at least 10 feet 3 04 m five 5 elbows Per Table 3 Only 16 feet of 4 vent pipe would be allowable wh...

Страница 10: ...e it can be disposed of properly Support vent piping with suitable hangers so its weight does not bear on the heater or building penetration and so that piping joints are not strained Support horizont...

Страница 11: ...wer A package of limestone gravel neutralizer is provided with the condensate assembly Remove the neutralizer from the packing and spread evenly throughout the tray and around the properly placed tube...

Страница 12: ...s control during testing When the heater is started check the supply pressure to verify that it is adequate during heater operation Undersize piping a restrictive fitting or an undersize gas meter can...

Страница 13: ...aune Vert Mauve GY Gray Gris COMB FAN Ventilateur combustion 115V 60Hz H0205500F IGN120 IND W W BK GY R BR TR TH DIGITAL IGNITION CONTROL BK Hi E2 Figure 15 Wiring diagram Hi E2 pool heater The Hi E2...

Страница 14: ...ff from a remote location Contact your local Jandy Pro Series distributor for information on the AquaLink RS control system to fit your back yard recreational needs An interrupt on off type remote can...

Страница 15: ...the brass fitting 5 Remove the temperature control sensor by removing the retainer bracket and its cap screws 6 Disconnect the limit switch wires from the limit switches The limit switches and the sho...

Страница 16: ...d A pressure relief valve is not supplied with the Hi E2 All equipment installations need to be in accordance with the manufacturers instructions To install a pressure relief valve 1 Remove the 3 4 br...

Страница 17: ...in the system when installing a PRV Any pressure relief valve installed must comply with provisions of the standard described in ANSI Z21 22 for the United Sates or CSA 4 4 in Canada Some local codes...

Страница 18: ...its operation and settings as outlined in the maintenance section of this manual 2 12 4 1 Step down Gas Pressure Regulator The step down regulator does not change requirements for gas supply piping o...

Страница 19: ...tem or a larger pump Before proceeding with either remedy verify proper heater operation Low gas input results in low temperature rise and vice versa A problem with the heater internal bypass assembly...

Страница 20: ...de of the service door and also on the inside of the control compartment door Lighting instructions are as follows 1 Turn off all electrical power to the heater at the main junction box 2 Open the con...

Страница 21: ...factor of the pool water between 7 4 and 7 6 See Table 7 for guidelines on other chemical measurements 3 4 2 Spas The proper chemical balance in spa water is more critical than in a swimming pool hea...

Страница 22: ...se spas or hot tubs 3 4 2 2 Saturation Index PH Total Alkalinity TA temperature Calcium Hardness and Total Dissolved Solids TDS play a role in whether the water is either corrosive or scale forming Th...

Страница 23: ...the 78 F 26 C level before expected usage keeping in mind to allow enough lead time for the water to reach the desired temperature 6 During the winter shut down the heater by following the lighting a...

Страница 24: ...technician when inspecting and servicing the heater To reactivate the heater in the spring have a qualified professional technician reassemble the heater as follows 1 Attach the pressure switch fitti...

Страница 25: ...lter and strainers aren t clogged that there are no mis positioned water valves that the gas or electric power supplies aren t shut off and that time clocks are properly adjusted Also be sure that the...

Страница 26: ...ixture monitors the flame and controls the combustion blower and gas valve When the temperature control requires heat the ignition control starts the blower providing a pre purge of the combustion cha...

Страница 27: ...tings or similar devices may be the problem Voltage outside of the above range may be due to poor wiring poor connections other loads such as air conditioning compressors or to an electric utility com...

Страница 28: ...ectrical power or setting the control to Off 4 5 2 3 Fireman Switch and External Interlocks Probe for voltage at point 3 the other connection of the terminal block which has a white wire connected to...

Страница 29: ...l for heat Observe that the normal sequence takes place by noting blower operation the glow of the igniter through the combustion chamber sight glass and then voltage at point 8 If the blower does not...

Страница 30: ...on heater The manometer will read zero until the gas valve opens and then it will indicate the gas orifice differential The gas orifice differential should be 4 0 0 3 WC for a unit at sea level See s...

Страница 31: ...other elevations Note that when the heater is operated with the gas valve off it will eventually lock out because the ignition control does not sense flame Normally there will be enough time to obtai...

Страница 32: ...ockage in the combustion air supply system Correct any such problems and verify normal operation by returning to the venturi system checkout procedures Pressure readings will be less if the heater is...

Страница 33: ...eration Check for blockage by disconnecting drainage tubes at the collector and the vent diffuser Probe these openings with a tool or wire hook to dislodge any debris Limestone gravel neutralizer is r...

Страница 34: ...04300 18 By Pass Valve Assembly 350 R0304400 19 Flow Control Cap 350 S0076700 20 By Pass Valve Gasket 350 R0011400 21 By Pass Valve Spring 350 R0304500 22 By Pass Valve Rod 350 R0304900 23 By Pass Val...

Страница 35: ...oor Exhaust Grill 350 R0348400 57 Indoor Vent Collar not shown 350 R0307900 58 Condensate Trap Assembly 350 R0303300 59 Limestone Gravel 350 R0306200 60 Condensate Trap Cover 350 R0213300 Venturi Hard...

Страница 36: ...ired Heater Installation Operation Manual 42 46 65 66 12 45 44 43 55 56 86 40 30 38 41 83 84 30A 34 32 33 39 36 37 35 6 4 10 1316 48 85 54 1 75 81 87 53 50 51 52 17 14 3 18 23 15 29 49 8 9 2 5 58 60 6...

Страница 37: ...Page 37 ENGLISH Jandy Pro Series Hi E2 and Hi E2R Gas Fired Heater Installation Operation Manual NOTES...

Страница 38: ...Page 38 ENGLISH Jandy Pro Series Hi E2 and Hi E2R Gas Fired Heater Installation Operation Manual NOTES...

Страница 39: ...Page 39 ENGLISH Jandy Pro Series Hi E2 and Hi E2R Gas Fired Heater Installation Operation Manual NOTES...

Страница 40: ...CA 92081 1 800 822 7933 www jandy com ZODIAC is a registered trademark of Zodiac International S A S U used under license All other trademarks referenced herein are the property of their respective ow...

Отзывы: