2.4. ROOM TEMPERATURE AND AIR EXCHANGE
2.5. REFRIGERATION POWER
For the air condensed refrigeration units, operating
room temperature must not exceed
32 °C
. The declared
performances are not guaranteed beyond this tempera-
ture.
For further details, see
Table 2.
Table 2
Table 3
If the power supply cable is damaged, it must
be replaced by the manufacturer or by the technical
assistance service or anyhow by a person with a
similar qualification, in order to avoid every risk!!!
MINIMUM AIR EXCHANGE
MODEL
ICY S
ICY M
ICY L
Power supply frequency (Hz)
AIR (m
3
/h)
50
60
50
60
50
60
800
1000
3100
3700
3100
3700
MODEL
Power supply frequency (Hz) Refrigeration output (W)
Declared values at evap. T.=-10°C, cond. T.=+40°C and power supply f.=50Hz.
Overheating in compliance with EN12900
Condensation power (W)
2.6. ELECTRICAL CONNECTION
Fig. 5
Fig. 6
•
•
•
•
Install a differential automatic circuit-breaker switch
upstream every appliance, according to the Standards
in force in the Country of installation.
The size of the connection cables must comply with the
information contained in the electric data of the technical
files. The voltage of the plants must be within the limit
of +10% and voltage unbalance of the phases must
not exceed 3%. The electric power connection must be
carried out by qualified personnel, in compliance with
the directives and laws of the country where the unit is
installed.
The power supply must be brought to the blast chiller
electrical control board, according to the data carried on
Table 4
.
The electrical power supply cables must have the cor-
rect size and be chosen depending on the real laying
conditions;
The electrical cables must enter and be blocked in
the appropriate cable sleeve and laid adequately
depending on the installation ambient;
Each conductor must be inserted in the corresponding
terminal;
The earth conductor must be connected directly to an
effective earthing system.
The manufacturing company declines all liability
and warranty obligations if persons are harmed or
appliances and objects damaged, due to incorrect
installation and/or lack of compliance with laws in
force.
ICY S
ICY M
ICY L
50
60
50
60
50
60
1458
2681
3987
4805
6146
7252
2248
2692
5871
7008
8989
10607